Test controller, Auto Adjust popup

AA1

This popup can be used to adjust a output (called control) until a input (Called target) reach a specific value. The output can be a electronic load, a power power supply, a ARB, etc.. The input can be any measuring device.

Contents
    Parameters
    Buttons
    Search patterns and results
    Scripting
Main page



Parameters

AA2


Buttons

AA3


Search patterns and results

In all cases the circuit is a 12V power supply with a 5ohm series resistor. The search works with or without logging activated.

FindMaxPower

The controlled value is the current (Blue trace) and the target is the power (Dark trace).
Find the maximum power to the target.

FindMaxVolt

The controlled value is the current (Blue trace) and the target is the voltage (Red trace).
Maximum voltage is when the current is minimum.

FindValue

The controlled value is the current (Blue trace) and the target is the voltage (Red trace).
Here the target is to get the voltage as close to 6V as possible by adjusting the current.

When a value is found a line is output to the log window:
Code:
;; Auto adjust Min: 1.99927 A   1.6230V   
;; Auto adjust Max: 1.70898 mA   11.9730V   
;; Auto adjust Value: 1.15503 A   5.9990V   Error: -0.0010  -167ppm

;; Auto adjust Max: 1.16772 A   6.943W   

Menu

The control value can be copied to the clipboard with a right click on the result line.



Scripting

This popup can be controlled with:

#setAutoAdjust "controlChannel" minRange maxRange minChange updateSpeed targetChannel min/max/value
#SHOWPOPUPSYSTEM AutoAdjust {x y {w h}}
#CLOSEALL